INPUT:
Voltage range Note.1 96-264VAC 120-370VDC
AC current 1.45A/115VAC 0.9A/230VAC
Frequency range 47-63Hz
Inrush current (max) 20A/115VAC 35A/230VAC
OUTPUT:
DC voltage (V) 12V 24V 48V
Efficiency 84% 87% 88%
Rated Current (A) 6.3A 3.2A 1.6A
Rated power(W) 75.6W 76.8W 76.8W
Voltage ADJ. range ±10%
Ripple & noise(max ) Note.2 80mVp-p 120mVp-p 150mVp-p
Voltage tolerange Note.4 ±2% ±1% ±1%
Line regulation ±0.5% ±0.5% ±0.5%
Setup, rise time 1200ms 60ms/230VAC 2000ms 60ms/115VAC(at full load)
Hold up time 60ms/230VAC 12ms/115VAC(at full load)
Status indicator Green LED
NOTE:
1.Derating may be needed under low input voltage.Please check the derating curve for more details.
2.Ripple & noise are measured at 20MHZ of bandwidth by using a “12”twisted pair-wire terminated with a 0.1uf & 47uf
parallel capacitor.
3.All parameters NOT specially mentioned are measured at 230VAC input,rated load and 25℃ of ambient temperature.
4.Tolerance:includes set up tolerance,line regulation and load regulation.
5.The ambient temperature derating of 3.5℃ /1000m with fanless models and of 5℃ /1000m with fan models for operating
altitude higher than 2000m(6500ft).
6.The power supply is considered a component which will be installed into a final equipment .The final equipment must be
re-confirmed that is still meets EMC directives
7.Installation clearances:40mm on top,20mm on the bottom,5mm on the left and right side are recommended when loaded
permanently with full power,In case the adjacent device is a heat source,15mm clearance is recommended