No. LED display Description Countermeasure
000 A parameter that requires power–down has
been specified.
Turn the power off, then back on.
011 The specified feedrate is zero. Check the feedrate parameter specified with a
function code.
013
The specified feedrate (maximum feedrate) is
zero.
Check the value of parameter No.043, which
indicates the maximum feedrate that can be
specified.
070 More than 32 blocks have been registered for a
buffering operation.
Reduce the number of registered blocks to 32.
085 Input from the reader/punch interface or the like
caused an overrun, parity, or framing error.
Correct the baud rate of the input/output unit
(always 4800) or other settings.
086
Input from the reader/punch interface or the like
includes an input/output unit operation ready
signal (DR) that is set to off.
Turn the reader/punch on. Check the cable connection.
087
After input from the reader/punch interface or
the like stops, character input does not stop
even though ten characters have been input.
Check the cable connection.
090
Reference position setting cannot be executed
normally.
Move the tool in the direction of reference position return in jog mode at a speed that causes
the servo position error to exceed 128. Then,
specify another reference position setting.
093
A first to third reference position return cannot
be executed because the reference position
has not yet been established.
Set the reference position.
224
The reference position has not yet been established. This occurs only when the ZRTN bit of
parameter No.001 is set to 0.
Set the reference position.
250 Input data 1 is invalid. Check input data 1, specified with a function
code.
251 Input data 2 is invalid. Check input data 2, specified with a function
code.
255
Operation cannot be activated because an
invalid mode is specified or because block
execution is in progress.
Check the mode. Check whether a block is
being executed.
290 The interface switch signal (DRC) was switched
during block execution.
Switch the signal after block execution stops.
B–65245EN/01
2. ALARM DISPLAY AND
CORRESPONDING
COUNTERMEASURES
TROUBLESHOOTING AND
COUNTERMEASURES
105
No. LED display Description Countermeasure
291
The speed of an axial movement specified by an
external pulse has exceeded the upper limit.
This occurs only when the EPEXA bit of parameter No.001 is set to 1.
Check the speed specified by the external
pulse. Check the magnification of the external
pulse (parameters No.062 and 063).
292
A checksum error for the battery–powered
memory was detected.
Parameters are cleared. Set the parameters
again. If this alarm subsequently recurs, replace
the unit.
Pulse coder alarms
No. LED display Description Countermeasure
300
A communication error (DTER) for the serial
pulse coder was detected.
Check the continuity of the signal cable. If the
cable is normal, the pulse coder may be defective. Turn the power off. If the alarm recurs when
the power is reapplied, replace the serial pulse
coder, together with the motor.
301
A communication error (CRCER) for the serial
pulse coder was detected.
Check the continuity of the signal cable. If the
cable is normal, the pulse coder or servo unit
may be defective. This error can also be caused
by external noise. See the chapter on noise
reduction in ”Connection.”
302
A communication error (STBER) for the serial
pulse coder was detected.
Check the continuity of the signal cable. If the
cable is normal, the pulse coder or servo unit
may be defective. This error can also be caused
by external noise. See the chapter on noise
reduction in ”Connection.”
303
An LED disconnection (LDAL) was detected in
the serial pulse coder.
Turn the power off. If this alarm recurs when the
power is reapplied, replace the motor.
304 A mispulse alarm (PMAL) for the serial pulse
coder was detected.
Turn the power off. If this alarm recurs when the
power is reapplied, replace the motor.
305
A miscount alarm (CMAL) for the serial pulse
coder was detected.
Turn the power off. If the alarm recurs when the
power is re–applied, replace the motor.
If the alarm does not recur, restart the operation
from reference position return.
306
The motor has overheated (OHAL). This alarm is issued when the amplifier has
overheated, causing the thermostat to trip.
Possible causes include an excessively high
ambient temperature and excessively strict
operating conditions. Check the actual cause.
Disconnect the power for about ten minutes,
then release the emergency stop state. If the
alarm recurs, replace the amplifier.
308 A soft phase alarm (SPHAL) was detected. Turn the power off. This alarm may be caused
by noise.
319
When the absolute pulse coder is used, the
motor has not yet rotated through more than one
turn after the first power–up.
Cause the motor to rotate through more than
one turn in jog feed mode, then turn the power
off then back on.
350
The battery voltage of the absolute pulse coder
is low.
Replace the battery.
Restart the operation from reference position
return.
351 The battery voltage of the absolute pulse coder
is low. (warning)
Replace the battery.
2 ALARM DISPLAY AND
CORRESPONDING
COUNTERMEASURES B–65245EN/01
TROUBLESHOOTING AND
COUNTERMEASURES
106
Servo alarms
No. LED display Description Countermeasure
400
The servo motor has overheated (estimated
value).
Turn the power off. After a while, turn the power
back on. Possible causes include an excessively high acceleration/deceleration frequency.
401 Servo amplifier ready signal (DRDY) went off.
403 The cooling fins have overheated. (hardware
detection)
The load on the motor may be too high. Re–examine the load conditions.
The regenerative discharge unit has overheated.
This alarm is issued when the average regenerative discharge energy is too high (when the
acceleration/deceleration frequency is too high,
for example).
404
When the regenerative discharge resistor is not being used, check whether a dummy connector
is fitted to the CX11–6 connector.
When the regenerative discharge resistor is being used,
(1) The average regenerative discharge energy may be too high. Decrease the acceleration/deceleration frequency.
(2) The thermostat line of the separate regenerative discharge unit may not be connected properly. Check the connection.
(3) The thermostat of the separate regenerative discharge unit may be defective. Disconnect the
separate regenerative discharge unit, then check the thermostat. If the thermostat is open even
through the separate regenerative discharge unit is cool, replace the separate regenerative
discharge unit.
If (1) to (3) are not the cause of the alarm, replace the servo amplifier.
405 Reference position return could not be
executed correctly.
Re–execute reference position return.
410
The servo position error in the stop state is
larger than the value specified in parameter
No.110.
Determine the mechanical cause of the large
position error. If no mechanical cause is found,
specify a larger value for the parameter.
411
The servo position error during movement is
larger than the value specified in parameter
No.182.
Determine the mechanical cause of the large
position error. If no mechanical cause is found,
apply any of the following countermeasures:
Specify a larger value for the parameter.
Specify a lower feedrate.
Increase the time constants.
An overcurrent alarm is issued. This alarm is issued when an excessively large
current flows in the main circuit.
412
(1) Check whether a valid motor number is specified in parameter No.30.
If yes, go to (2).
(2) Check whether the standard values are specified in the current control parameters for servo
control.
Correct current control is possible only when the standard values are specified for the following
parameters:
No.70, 71, 72, 78, 79, 84, 85, 86, 87, 88, 89, 90
(3) Disconnect the power line from the amplifier connector. Then, release the emergency stop
state.
– If the overcurrent alarm continues to be issued, replace the amplifier.
– If no overcurrent alarm is issued, go to (4).
(4) Disconnect the power line from the amplifier connector. Check the insulation between the
ground and each of U, V, and W. If the insulation is satisfactory, go to (5).
If a short–circuit is detected, disconnect the power line from the motor connector. Then, check
the insulation between the ground and each of U, V, and W of the motor.
If a short–circuit is found between the ground and U, V, or W of the motor, replace the motor.
If the insulation is satisfactory, replace the power line.
(5) Connect the power line. Observe the waveform of the motor current (IR, IS) while the motor is
accelerating or decelerating. See the description of the checking of the motor current in Appendix E, ”Servo Check Board”. If the motor current (IR, IS) does not exhibit a normal sine wave,
replace the amplifier.
(6) If (1) to (4) above are not the cause of the alarm, the pulse coder, command cable, or internal
hardware of the CNC may be defective.
B–65245EN/01
2. ALARM DISPLAY AND
CORRESPONDING
COUNTERMEASURES
TROUBLESHOOTING AND
COUNTERMEASURES
107
No. LED display Description Countermeasure
A DC link overvoltage alarm is issued. This alarm is issued when the DC voltage of the
main circuit power is too high.
413
(1) The supply voltage for dynamic power may exceed the rated value. Check the voltage. If the
voltage is too high, reduce the voltage to an appropriate level.
(2) The regenerative discharge unit may not be properly connected. Check the connection.
(3) The resistance of the separate regenerative discharge unit may be abnormal. Disconnect the
separate regenerative discharge unit, then check the resistance. If the resistance is not within
+20% of the predetermined resistance, replace the separate regenerative discharge unit.
If (1) to (3) are not the cause of the alarm, replace the servo amplifier.
A DC link low voltage alarm is issued. This alarm is issued when the DC voltage of the
main circuit power is too low.
414 (1) The external circuit breaker may be turned off. Check the circuit breaker.
(2) The supply voltage for dynamic power is lower than the rated value. Check the voltage. If the
voltage is too low, increase it to an appropriate level.
(3) The external magnetic contactor may not be connected properly. Check the connection.
If (1) to (3) are not the cause of the alarm, replace the servo amplifier.
417
A parameter has been specified incorrectly. Check the following parameters:
No.30: Is the specified motor type correct?
No.31: Is the specified direction of rotation of the
motor correct?
No.106: Is the denominator of the number of
pulses per single revolution of the motor 0?
No.180: Is the specified reference counter
capacity 0 or a negative value?
418 A DO alarm is issued. Replace the servo unit.
423 The specified speed exceeds 32767000 detection units per second.
Re–examine the CMR and speed settings.
The cooling fan has stopped. This alarm is issued when the fan motor built into
the servo amplifier has failed.
425 (1) Check that the fan is not clogged with foreign matter.
(2) Check that the power connector of the fan is connected properly.
(3) Replace the fan or servo unit.
Overtravel alarms
No. LED display Description Countermeasure
500 The positive stroke limit has been exceeded. Check whether *+OT and *–OT are connected
correctly. Check whether a correct move com501 The negative stroke limit has been exceeded. mand is specified. Move the tool in the opposite
direction in jog mode, then perform a reset.
510 The positive soft stroke limit has been
exceeded.
Check whether appropriate values have been
specified for parameters No.142 and 143.
Check whether a valid move command is speci511 The negative soft stroke limit has been
exceeded.
Check whether a valid move command is s ecified. Move the tool in the opposite direction in jog
mode, then perform a reset.
2 ALARM DISPLAY AND
CORRESPONDING
COUNTERMEASURES B–65245EN/01
TROUBLESHOOTING AND
COUNTERMEASURES
108
System alarms
No. LED display Description Countermeasure
– An error was detected in the RAM write/read test
at power–up.
Replace the unit.
–
An error was detected in the data collation
check for the battery–powered memory.
Turn the power off then back on. Then, re–enter
the parameters. If this alarm recurs, replace the
unit.
– A data transfer alarm for the battery–powered
memory has been issued.
Replace the unit.
– A watchdog alarm was issued. Turn the power off then back on. If this alarm
recurs, replace the unit.
– A checksum alarm for the control software ROM
is issued.
Replace the unit.
– A checksum alarm for the ROM that is built into
the CPU is issued.
Replace the unit.
– An error was detected in the control circuit. Replace the unit.
I/O link alarm
No. LED display Description Countermeasure
–
A FANUC I/O link error occurred. A unit connected to the line was turned off.
Turn off the power to all units connected to the
line. Then, turn on the slave devices, followed
by the master device.
No LED display
No. LED display Description Countermeasure
– No indicators lit
The control circuit is not operating normally. (1) Check the 24–VDC control supply voltage.
If the voltage is low, increase the voltage to
an appropriate level.
(2) Check whether a fuse in the servo unit has
blown. If a blown fuse is found, replace it, following the procedure described in Section 3,
”Replacing Fuse.”
If (1) and (2) are not the cause, replace the servo
amplifier.
Các Mã Lỗi Của Drive Bê Ta Fanuc – Dịch Vụ Cung Cấp Linh Kiện Sửa Chữa Fanuc Tại Bến Cát Bình Dương
HỖ TRỢ TRỰC TUYẾN
Kinh Doanh: 0937029193
Giờ Làm Việc: 8h đến 18h từ thứ 2 đến thứ 7.
Danh mục: Vật Tư Máy CNC
Mô tả